Minimum circuit ampacity calculator
Enter the compressor RLA and the fan and blower FLA from the nameplate to get the minimum circuit ampacity, the maximum fuse or breaker, and the copper wire size, worked the way NEC Article 440 does it.
Inputs
Result
- Minimum circuit ampacity
- 24.45 A
- Max fuse or breaker
- 40 A — 225% rule, 43.05 A rounded down
- Try first
- 30 A — 175% rule, 33.75 A rounded down
- Smallest breaker that holds the MCA
- 25 A
- Copper conductor, 75 °C
- 12 AWG (25 A)
Yes, 12 AWG on a 40 A breaker is legal here. The usual 20 A limit for that wire (240.4(D)) does not apply to motor-compressor circuits: NEC 440.22 sizes the breaker for the compressor's starting current, and the wire is sized to the MCA. Where the unit's nameplate gives an MCA and a max fuse/breaker, those govern (110.3(B)); this works them out from the component amps when the plate is missing, unreadable, or you are checking it. Long runs may need a bigger wire for voltage drop — check with the voltage drop calculator.
How the MCA adds up
Every motor at its nameplate current, the largest at 125%, and electric heat at 125%.
| Load | Nameplate A | Counted as A |
|---|---|---|
| Compressor (largest) | 18.6 | 23.25 |
| Condenser fan | 1.2 | 1.20 |
| Minimum circuit ampacity | 24.45 |
What MCA and MOCP mean on a nameplate
Every condenser, heat pump and air handler carries two electrical figures. Minimum circuit ampacity (MCA) is the smallest current the branch circuit's wire must be able to carry. Maximum overcurrent protection (MOCP), printed as "Max fuse/breaker", is the largest fuse or breaker you may put on it. Wire is sized to the first, the breaker can be anything up to the second.
Why a small wire on a big breaker is legal here
A unit with an 18.6 A compressor and a 1.2 A fan has an MCA of 24.45 A and a maximum breaker of 40 A. That means 12 AWG copper on a 40 A breaker, which looks wrong to anyone used to the 20 A limit for 12 AWG. It is correct.
The ordinary limits in 240.4(D) protect wire from overload. A compressor has its own overload protection built in, so the breaker on its circuit only has to protect against short circuits and ground faults, and it has to be large enough to let the compressor start. NEC 440.22 therefore lets the breaker exceed the small-conductor limits, and the wire only has to carry the MCA.
175% or 225%?
The code starts at 175% of the largest motor's rated current and allows up to 225% if the smaller breaker trips on start. Equipment nameplates usually print the 225% figure, rounded down, as the maximum. Using the nameplate maximum is permitted and gives the compressor the most room to start; a smaller standard breaker that still holds the MCA is also fine.
Heat strips change the picture
Electric heat is a continuous resistive load with no starting surge, so it is counted at 125% and the 225% allowance does nothing for it. On an air handler with large strips the 225% figure can come out below the MCA. The calculator then moves the breaker up to the next standard size at or above the MCA and tells you so. For these units the nameplate is the authority; heat circuits also fall under Article 424.
Exam-style minimum ampacity questions, worked
These turn up in NEC exam prep and in the Article 440 sections of licensing tests. The wording changes; the method does not. Each answer below is produced by the calculator above.
An air conditioner: compressor RLA plus a fan FLA
440.33 counts every motor at its rated current and adds 25% of the largest one. There is no rounding in the calculation itself.
| Compressor RLA | Fan FLA | MCA | Copper at 75 °C | Max fuse/breaker |
|---|---|---|---|---|
| 59.6 A | 3.5 A | 78 A | 4 AWG (85 A) | 125 A |
| 42.8 A | 2.7 A | 56.2 A | 6 AWG (65 A) | 90 A |
| 34.2 A | 2.3 A | 45.05 A | 8 AWG (50 A) | 70 A |
Worked for the first row: 1.25 × 59.6 = 74.5, plus 3.5 = 78 A. The fan is not increased; only the largest motor is.
When the plate gives a branch-circuit selection current
440.32 sizes the conductors to a single motor-compressor at 125% of either the rated-load current or the branch-circuit selection current, whichever is greater. A compressor marked RLA 43.9 A with a BCSC of 46.4 A is therefore worked from the BCSC: 1.25 × 46.4 = 58 A, which needs 6 AWG copper at 75 °C (65 A). Using the RLA instead is the single most common mistake on these questions.
The same rule covers a larger compressor on its own individual branch circuit: a 25 hp three-phase compressor with a full-load rating of 42 A and a branch-circuit selection current of 45 A gives 1.25 × 45 = 56.25 A. The horsepower and the voltage are not used — 440.32 works from the marked current, not from Table 430.250.
Sizing the disconnect, not the circuit
A disconnecting means is a different rule again. Where it serves a motor-compressor together with other loads, 440.12(B)(2) sets the rating at 115% of the sum of all currents at the rated-load condition — not 125%, and nothing is singled out as largest. For a compressor at 47.3 A with a fan at 5.9 A: 1.15 × (47.3 + 5.9) = 1.15 × 53.2 = 61.18 A.
Four current-carrying conductors and a nonlinear load
This one is not Article 440 at all. The ampacity in Table 310.16 assumes no more than three current-carrying conductors in a raceway or cable; past that, Table 310.15(C)(1) applies an adjustment factor — 80% for four to six. A nonlinear load is what puts the neutral into the count, because harmonic current flows in it.
Work it backwards: the conductor's table ampacity must be the load divided by the factor, not the load itself. 44 A ÷ 0.8 = 55 A of table ampacity needed. At 75 °C, 8 AWG copper carries only 50 A, so the answer is 6 AWG copper, which carries 65 A. Dividing is the step people miss; multiplying 44 by 0.8 gives 35.2 and the wrong, smaller wire.
What rounding is allowed
Where a calculation ends in a fraction of an ampere below 0.5, 220.5(B) permits it to be dropped. An MCA that works out to 20.45 A may therefore be treated as 20 A, and a 20 A branch circuit is the minimum permitted. At 0.5 and above it goes up instead. Questions that say “do not round” want the exact figure, decimals and all.
Questions
What is minimum circuit ampacity?
The smallest current the branch-circuit conductors to a piece of equipment must be able to carry. For air conditioning it is the sum of the motor currents with the largest increased by 25%, plus any electric heat at 125%. Size the wire to it; do not size the breaker to it.
How do I calculate MCA for an air conditioner?
Take the compressor's rated load amps (RLA), multiply by 1.25, and add the condenser fan's full load amps (FLA). A compressor at 18.6 A with a 1.2 A fan gives 1.25 × 18.6 + 1.2 = 24.45 A.
What is the minimum circuit ampacity for a compressor with an RLA of 59.6 amperes and a fan motor with an FLA of 3.5 amperes?
78 A. NEC 440.33 takes 125% of the largest motor plus every other motor at full value: 1.25 × 59.6 = 74.5, plus 3.5 = 78 amperes exactly, with nothing to round. Those conductors need 4 AWG copper at 75 °C (85 A). The maximum fuse or breaker is a separate figure: 225% of the largest plus the rest is 137.6 A, which rounds down to a 125 A standard size.
Is this an MOCP calculator too?
Yes. Every result includes the maximum overcurrent protection — the largest fuse or breaker the equipment permits — alongside the MCA and the wire size. MOCP comes from NEC 440.22: 175% of the largest motor plus the other loads, raised to 225% where the smaller size will not start the compressor, then rounded down to a standard size from 240.6(A).
What is the minimum circuit ampacity for a compressor with an RLA of 42.8 amperes and a fan motor with an FLA of 2.7 amperes?
56.2 A. 1.25 × 42.8 = 53.5, plus 2.7 = 56.2 amperes (NEC 440.33). That needs 6 AWG copper at 75 °C, which carries 65 A.
What is the minimum circuit ampacity for a compressor with an RLA of 34.2 amperes and a fan motor with an FLA of 2.3 amperes?
45.05 A. 1.25 × 34.2 = 42.75, plus 2.3 = 45.05 amperes. 8 AWG copper at 75 °C (50 A) covers it.
What is the minimum circuit ampacity for a compressor marked with a branch-circuit selection current larger than its rated load current?
Use the branch-circuit selection current, because NEC 440.32 says whichever is greater. A compressor with an RLA of 43.9 A and a BCSC of 46.4 A gives 1.25 × 46.4 = 58 A, not 54.9 A. Working from the RLA is the usual wrong answer.
What is the minimum ampacity for a disconnect serving a compressor and a fan motor?
115% of the sum of every current at the rated-load condition, under NEC 440.12(B)(2). For a compressor at 47.3 A and a fan at 5.9 A: 1.15 × 53.2 = 61.18 A. Note the disconnect uses 115% and the sum of everything, where the branch circuit uses 125% and only the largest motor.
A 44 A nonlinear load has four current-carrying conductors at 75 degrees C. What size conductor is required?
6 AWG copper. Four current-carrying conductors bring in the 80% adjustment factor from NEC Table 310.15(C)(1), and a nonlinear load makes the neutral one of the four. Divide rather than multiply: 44 ÷ 0.8 = 55 A of table ampacity required. 8 AWG carries only 50 A at 75 °C, so 6 AWG is the smallest that qualifies.
If a minimum ampacity calculation comes to 20.45 amperes, what size branch circuit is permitted?
20 A. NEC 220.5(B) permits a fraction of an ampere below 0.5 to be dropped, so 20.45 A may be treated as 20 A. Had it come to 20.55 A it would go up instead. Where a question says “do not round”, give the exact figure.
What is the difference between MCA and MOCP?
MCA sizes the wire; MOCP, the max fuse or breaker, sizes the protection. MOCP is always the larger figure, often much larger, because the breaker on a compressor circuit has to let the compressor start, while its own internal overload protects it from overheating.
Can I use a 40 amp breaker on 12 gauge wire for an AC unit?
Yes, if the unit's MCA is 25 A or less with 75 °C terminals and its maximum fuse/breaker is 40 A or more. NEC 440.22 allows a compressor circuit's breaker to exceed the normal 20 A limit for 12 AWG, because the wire is protected from overload by the compressor's own protection.
Should I use the max breaker size or a smaller one?
Either is allowed, as long as the breaker is at least large enough to carry the MCA and no larger than the maximum. The nameplate maximum gives the compressor the most room to start without nuisance trips, which is why most installers use it.
Why does my air handler's breaker look too small for the heat strips?
It may not be. Heat strips are counted at 125% in the MCA and get no starting allowance, so on a heat-heavy air handler the breaker is sized up from the MCA rather than down from 225%. Follow the nameplate, which covers each heat kit option separately.
Sources
- NFPA 70, National Electrical Code (NEC). National Fire Protection Association. Free read-only access with a free NFPA account.
Codes are adopted and amended locally. Check the edition in force where you work.
More Electrical calculators
Voltage drop calculator
Drop in volts and percent for copper or aluminum, single-phase, three-phase or DC.
Conduit fill calculator
Fill percentage and the smallest EMT, rigid or PVC conduit for a mix of THHN conductors.
Recessed lighting calculator
How many can lights a room needs, the spacing, where each one goes from the wall, and whether that hits the light level the room wants.
Electrical load calculator
Dwelling service size by the NEC 220.82 optional method, with every demand factor shown.
Wire size & ampacity calculator
Conductor size and breaker from the load, with ambient correction and bundling adjustment applied.
Box fill calculator
Box fill volume by NEC 314.16 for any mix of wires, devices, clamps and grounds, and which boxes are big enough.
Watts to amps calculator
Convert watts to amps for DC, single-phase and three-phase power, with power factor and the breaker it needs.
Amps to watts calculator
Convert amps to watts, kilowatts and VA at any voltage, DC or AC, single- or three-phase.
kVA calculator
kVA to amps, amps to kVA and kW to kVA, single- or three-phase, with the next standard transformer size.
Generator sizing calculator
The generator size a house actually needs, counting one motor start at a time instead of all of them at once.
Breaker size calculator
The breaker a load or motor needs, with the 125% continuous rule, the motor tables and the wire that goes with it.
Electricity cost calculator
What an appliance or a whole list of them costs to run per hour, day, month and year, at your state’s average rate or your own.
EV charging cost calculator
What it costs to charge an electric car at home, at public chargers and at fast chargers, per mile and per month, compared with gas.
Space heater cost calculator
What a space heater costs to run per hour, day, month and winter, and how much electricity it really uses, at your state’s rate.