RoughInSizing calculators for the trades

Generator sizing calculator

Add what you need to keep running and get the generator size. Motor starting surges are counted properly, one at a time, so you are not sold twice the generator you need.

Running and starting wattsOne motor start at a timeAltitude and heat derates

Inputs

What has to run at the same time
Only what runs together. A generator covering the whole house at once is far bigger than one covering what you actually need in an outage.
ft
Engines lose output with thin air above about 1,000 ft.
°F
Hot air is thin air. Use your summer design temperature.
%
Leave at 100% for watts. Use 80% to see the kVA a spec sheet would quote.

Result

Generator size
4kW generator
2,800 W running, 4,800 W at the worst start (well pump, 1/2 hp)
Total running watts
2,800 W
Hardest single start
Well pump, 1/2 hp — adds 2,000 W
Peak demand
4,800 W — running total plus that one start
Nameplate for the running load
3,500 W — at 80% load
Nameplate to surge to the peak
3,840 W — sets surge to about 25% over nameplate
Governed by
the starting load, so you need at least 3,840 W of nameplate
If you summed every surge
7,850 W — what most calculators do, 64% too big

Your peak is 4,800 W, so check the generator's quoted starting watts clear that figure — the running and starting ratings are listed separately and a set can meet one and fail the other. Here the motor start is what sets the size, not the running load. A 4,000 W set leaves your 2,800 W running load at 70% of nameplate. Size the feeder and transfer switch with the wire size calculator.

Where the watts go

Running watts are what each load draws continuously. The last column is the extra a motor needs at the instant it starts, over and above its running draw. Only the largest of those counts, which is the row marked below.

ApplianceQtyRunning WExtra to start
Refrigerator / freezer17001,500
Furnace blower, 1/2 hp18001,550
Well pump, 1/2 hp11,0002,000
Lights, 10 LED3300—
Total2,8002,000

The mistake that sells people twice the generator

Nearly every generator calculator adds up the starting watts of everything on your list. That is wrong, and it is wrong in the direction that costs you money.

Motors do not all start at the same instant. Your fridge compressor kicks in, finishes, and some minutes later the well pump starts. The worst moment your generator will ever see is everything running steadily while the single hardest-starting motor kicks in.

peak = total running watts + the largest single (starting − running)

Two identical fridges do not need two surges of headroom; they need one. The results above show what the summed-surge method would have told you, and the gap is often 50% or more. On a home standby unit that difference is thousands of dollars and a bigger gas line.

Running watts and starting watts are two different ratings

A generator is advertised with both, something like 7,500 running and 9,500 starting. Your running load has to fit inside the first and your peak inside the second, and a unit can easily pass one test and fail the other. Check them separately.

Do not plan on using all of it

A generator should carry a continuous load of about 80% of its rating. Running flat out leaves nothing for a motor start, makes the set hot and noisy, and shortens its life. The sizing above already builds that margin in, which is why the recommended size looks larger than your running total.

The opposite case matters too, especially on diesel. Running a diesel set at under about a third of its rating for long periods causes wet stacking, where unburnt fuel fouls the exhaust. Oversizing is not a free safety margin.

Whole house generator sizing

“Whole house” means two quite different things, and the size follows from which one you want.

A managed whole-house standby set runs everything, but not all at once: a load-management module sheds the air conditioner while the well pump starts, or locks out the second AC stage while the range is on. That is how a 20 kW set covers a house whose connected load adds up to far more. An unmanaged whole-house set has to carry every load that could coincide, which for a typical house with central air, an electric water heater and a well pump means 24 kW and up.

For a standby set the sizing load is the whole panel, not the few circuits you would run on an extension cord. Count the air conditioner or heat pump, which is nearly always the largest starting load; electric water heating, range and dryer if you have them; the furnace blower, well pump and sump pump; the fridge and freezer; and lighting and electronics, which are small. Then apply the one-motor-at-a-time rule above: everything’s running watts plus the single largest starting surge.

Standby sets are sized in whole steps, typically 10, 14, 18, 22 and 26 kW for air-cooled units, with liquid-cooled sets above that. Pick the step at or above the figure the calculator gives, then check the altitude and temperature derate below — at 5,000 ft a 22 kW set is doing the work of about 19 kW.

What size generator to run a furnace

A gas furnace needs only its blower, igniter and controls, not heat: typically 600 to 800 running watts with a surge of 1,500 to 2,500 as the blower starts, so a small portable of 3 to 4 kW runs one comfortably with room for a fridge and lights. An electric furnace is a different machine entirely — the heat strips alone are 10 to 20 kW — and is rarely worth backing up; most people on electric heat run a space heater or two on a portable instead. A heat pump is sized by its compressor’s starting surge, the same as central air.

Commercial and three-phase sets

The same arithmetic holds, but the loads do not: three-phase motors, lifts, compressors and kitchen equipment, often with soft starters or VFDs that cut the starting surge dramatically and change the answer. Commercial standby also runs into fire and life-safety requirements that dictate the set and its transfer equipment regardless of the load. This calculator covers single-phase residential loads; a commercial standby set should be sized from a measured load study and the relevant code, not from a table of typical appliances.

Altitude and heat both cost you output

altitude: about 3% per 1,000 ft above 1,000 ft heat: about 1% per 10 °F above 77 °F

Thin air means less oxygen and less power. In Denver on a 95 °F afternoon a generator delivers around 86% of its sea-level nameplate, so a set that was exactly right at sea level is now undersized. These are typical rules of thumb; where you have the manufacturer's derate curve, use theirs instead.

Watts on a plate are not always the truth. Appliance figures here are typical, not yours. A motor's real inrush depends on its design and how hard it starts under load, and the honest number is the locked rotor amps on the nameplate. If you are sizing a standby set for a whole house, have the installer do a measured load study rather than trusting any web calculator, this one included.

Questions

What size generator do I need to run a house?

It depends entirely on what you need running at once, not the size of the house. A fridge, furnace blower, well pump and some lights comes to about 2,800 running watts and a 4,800 watt peak, which needs a 4 kW set — sized by the well pump's start rather than the running load. Adding central air conditioning or an electric water heater pushes you toward 14 to 20 kW, because those are large continuous loads.

What size whole house generator do I need?

For a house with central air, an electric water heater and a well pump, typically 20 to 26 kW unmanaged, or around 14 to 20 kW with a load-management module that sheds the air conditioner while other large loads start. Without central air or electric water heating, 10 to 14 kW usually covers a whole house. Size it from the running watts of everything that could be on together plus the single largest starting surge, then allow for altitude and heat.

How big a generator do I need to run a furnace?

A gas furnace needs only its blower and controls: about 600 to 800 running watts with a 1,500 to 2,500 watt surge, so a 3 to 4 kW portable runs one with a fridge and lights alongside. An electric furnace is not comparable — its heat strips draw 10 to 20 kW on their own.

Do I add up all the starting watts?

No, and this is the single most common error. Motors start at different times, so you need your total running watts plus the extra demanded by the one hardest-starting motor. Summing every surge typically overstates the requirement by half or more.

What is the difference between running and starting watts?

Running watts are the continuous draw. Starting watts are the brief surge a motor pulls as it spins up, often two to three times its running figure. Resistive loads such as heaters, kettles and incandescent lights have no surge at all; anything with a motor or compressor does.

Can I run my generator at full capacity?

Not continuously. Aim for about 80% of the rating, which leaves headroom for motor starts and keeps the set from overheating. On a diesel set, avoid the other extreme as well: long periods below about a third load cause wet stacking.

Does altitude affect generator size?

Yes, and people forget it. Reckon on losing about 3% of output per 1,000 feet above 1,000 feet, plus roughly 1% per 10 °F above 77 °F. At 5,000 feet on a hot day you have lost something like 14% of the nameplate, so the generator has to be correspondingly larger.

What is the difference between kW and kVA?

kW is real power, kVA is apparent power, and they are related by the power factor. Generators are commonly rated at 0.8 power factor, so a 20 kW set is quoted as 25 kVA. For a house of ordinary appliances, size in watts and treat kVA as the spec-sheet translation.

Sources and method: Method: typical altitude and temperature derates. The generator's own rating governs. The full list, with the calculators that use each source, is on the sources page.

Sources

  • Typical altitude and temperature derates for engine generators. Industry practice; the generator's own rating governs.

More Electrical calculators

Voltage drop calculator

Drop in volts and percent for copper or aluminum, single-phase, three-phase or DC.

Conduit fill calculator

Fill percentage and the smallest EMT, rigid or PVC conduit for a mix of THHN conductors.

Recessed lighting calculator

How many can lights a room needs, the spacing, where each one goes from the wall, and whether that hits the light level the room wants.

Electrical load calculator

Dwelling service size by the NEC 220.82 optional method, with every demand factor shown.

Wire size & ampacity calculator

Conductor size and breaker from the load, with ambient correction and bundling adjustment applied.

Minimum circuit ampacity calculator

MCA, max breaker and wire size for an AC condenser, heat pump or air handler, from the nameplate amps.

Box fill calculator

Box fill volume by NEC 314.16 for any mix of wires, devices, clamps and grounds, and which boxes are big enough.

Watts to amps calculator

Convert watts to amps for DC, single-phase and three-phase power, with power factor and the breaker it needs.

Amps to watts calculator

Convert amps to watts, kilowatts and VA at any voltage, DC or AC, single- or three-phase.

kVA calculator

kVA to amps, amps to kVA and kW to kVA, single- or three-phase, with the next standard transformer size.

Breaker size calculator

The breaker a load or motor needs, with the 125% continuous rule, the motor tables and the wire that goes with it.

Electricity cost calculator

What an appliance or a whole list of them costs to run per hour, day, month and year, at your state’s average rate or your own.

EV charging cost calculator

What it costs to charge an electric car at home, at public chargers and at fast chargers, per mile and per month, compared with gas.

Space heater cost calculator

What a space heater costs to run per hour, day, month and winter, and how much electricity it really uses, at your state’s rate.

Other trades