Header size calculator

Enter the rough opening width and what the wall holds up. You get the smallest header from the IRC span tables that will carry it, the jack and king studs it needs at each end, every other size that works, and the full span table for your load.

IRC Tables R602.7(1) and (2)Jack and king studsExterior and interior wallsHeader span chart

Inputs

ft
A 36 in door is about 3 ft 2 in rough; a 16 ft garage door, 16 ft 3 in.
in
From your building department. Below 30, the table uses 30.
For the king studs, IRC Table R602.7.5.
ft
Perpendicular to the ridge. 12 to 36 ft; widths between are interpolated.

Result

Header
—
Every size for this opening
HeaderMax spanJacks each end

Header span table

Header12 ft wide24 ft wide36 ft wide

Spans in feet and inches, with the number of jack studs needed at each end in brackets. From 2021 IRC Tables R602.7(1), exterior bearing walls, and R602.7(2), interior bearing walls; No. 2 Douglas fir-larch, hem-fir, Southern pine and spruce-pine-fir.

How it is worked out

The IRC's header table gives the longest span each header can carry for five load cases, three ground snow loads and three building widths, with the number of jack studs needed under each end. The calculator looks up your column, interpolating between building widths as the table's note c allows, and lists every header that spans your opening. It picks the one needing the fewest jack studs, then the least lumber, among those that fit in the wall.

A 6 ft window in a one-storey house 24 ft wide, with ground snow of 30 psf or less: a 2-2x10 header spans 6 ft 10 in and needs two jack studs at each end. It is 6 ft plus 2 x 2 x 1-1/2 in long: 6 ft 6 in.

Reading the header sizes

  • 2-2x10 means two 2x10s, nailed together with a 1/2 in spacer between them so they are as thick as a 2x4 wall (3-1/2 in).
  • 3-2x10 is three 2x10s, 4-1/2 in thick, which needs a 2x6 wall.
  • 1-2x8 is a single 2x8 on edge, which leaves room for insulation in the rest of the wall thickness.

Jack studs and king studs

Jack (trimmer) studs carry the header down to the bottom plate. The number at each end comes from the table: wider openings and heavier loads need two or three. Where only one is needed, the table's note d allows an approved framing anchor to the king stud in place of the jack.

King studs run full height beside the jacks and resist the wind pushing on the wall around the opening. IRC Table R602.7.5 sets how many at each end of a header in an exterior wall:

Header span up toWind under 140 mph, Exp. B, or 130 mph, Exp. CWind 115 mph or less, Exp. B
4 ft11
6 ft21
8 ft21
10 ft32
12 ft32
14 ft32
16 ft42
18 ft42

Spans between those listed use the next larger row. Where a framing anchor replaces a jack stud, use the first column whatever the wind speed.

What the table does not cover

Interior bearing walls use Table R602.7(2), which the calculator includes for walls carrying one or two floors; interior walls carrying roof loads need a design. Beyond that, the tables do not cover openings wider than the largest header in the column, buildings over 36 ft wide, ground snow over 70 psf, or point loads from girders or posts above. Those need an engineered header, often LVL, sized by the manufacturer's tables or a designer. If cripple studs bear on the header so its top is not braced, 2x8, 2x10 and 2x12 headers carry only 70% of the table span (note f).

To count the studs for the whole wall, kings and jacks included, use the stud calculator.

Questions

What size header do I need for a 6 foot opening?

In a one-storey house 24 ft wide with ground snow up to 30 psf, a 2-2x10 header with two jack studs at each end, from IRC Table R602.7(1). With a floor above it bearing on a center wall, a 2-2x12 with two jacks.

What size header for a 3 foot door?

For a 36 in door, about a 38 in rough opening, a 2-2x6 header with one jack stud at each end carries a roof and ceiling in a building 24 ft wide with snow up to 30 psf, and a floor above as well where the floor bears on a center wall.

How far can a double 2x12 header span?

On an exterior wall carrying only the roof and ceiling, with ground snow up to 30 psf: 10 ft 7 in for a building 12 ft wide, 8 ft 1 in at 24 ft and 6 ft 10 in at 36 ft. Under a floor bearing on a center wall, 8 ft 6 in, 6 ft 8 in and 5 ft 8 in.

What size header for a 16 foot garage door?

No 2x lumber header in IRC Table R602.7(1) spans 16 ft; the largest, 4-2x12, reaches 15 ft 3 in for a 12 ft wide building under roof only. Garage door headers that wide are usually LVL or glulam, sized from the manufacturer's tables.

How many jack studs do I need?

The table gives it with each header: one per end for short headers under light loads, up to four for wide headers under two floors and heavy snow. One jack may be replaced by an approved framing anchor.

How many king studs do I need at a header?

In an exterior wall, IRC Table R602.7.5 gives 1 king stud per end for headers up to 4 ft, 2 up to 8 ft, 3 up to 14 ft and 4 up to 18 ft where the design wind speed is under 140 mph in Exposure B. Where it is 115 mph or less in Exposure B, 1 up to 8 ft and 2 up to 18 ft.

How long should a header be?

The rough opening width plus 1-1/2 in for each jack stud at each end. With one jack each side, the opening plus 3 in.

More Carpentry calculators

Stair stringer calculator

Risers, treads, stringer length and a cut list from the total rise, checked against the IRC or IBC stair rules.

Fence calculator

Posts, pickets, rails and post-hole concrete for a wood fence, from the length of each run and the gates.

Deck board calculator

Deck boards, linear feet, screws or hidden clips for a deck of any size, straight or diagonal.

Stud calculator

Studs, plates and precut stud length for any set of walls, with corners, intersections, doors and windows, and the cost.

Plywood calculator

Sheets of plywood or OSB for walls, floors or any area, with waste, weight per sheet and the cost.

Floor joist span calculator

Maximum floor and ceiling joist spans by species, grade, size and spacing, worked from the AWC 2024 span tables and design values.

Rafter span calculator

Maximum rafter span for roof live or snow load, by species, grade, size and spacing, from the AWC 2024 span tables.

Deck joist span calculator

Maximum deck joist span and overhang by species, size and spacing, from the AWC DCA 6 tables, with a check of your span.

Deck beam span calculator

Maximum deck beam span for every beam size by the joist span it carries, and the posts each beam needs, from AWC DCA 6.

Deck footing calculator

Footing size and thickness, maximum 6x6 post height and concrete for deck posts, from AWC DCA 6 Table 4.

Baluster spacing calculator

How many balusters a railing needs and the exact gap between them, kept under the IRC's 4 inch sphere rule.

Board foot calculator

Board feet for any list of lumber, with price, plus Doyle, Scribner and International log scales.

Other trades