Box fill calculator

Enter what goes in the box. You get the volume the NEC requires, line by line, and every standard metal box that holds it. For plastic boxes, enter the volume stamped inside.

NEC 314.16(B) allowancesTable 314.16(A) boxesNEC 2020+ ground rule

Inputs

Insulated wires entering the box
Count hots and neutrals, not grounds. A 14/2 cable is 2 wires; 14/3 is 3. A wire that loops through unbroken counts once, or twice if the loop is 12 in or longer.
All equipment grounds together count as one, plus a quarter for each over four.
Each counts as two wires of the size connected to it.
Internal cable clamps
Each counts as one of the largest wire.
Plastic boxes are marked with their volume inside; choose "Marked volume" and enter it.
cu in
cu in
Add the volume marked on it, if any.

Result

Box fill required
—
ItemCounts ascu in

Metal box volumes

NEC Table 314.16(A). Green rows hold what you entered.

Box (inches)Volume, cu in14 AWG max12 AWG max

Volume per conductor

NEC Table 314.16(B).

Wire sizecu in each
18 AWG1.50
16 AWG1.75
14 AWG2.00
12 AWG2.25
10 AWG2.50
8 AWG3.00
6 AWG5.00

How box fill is counted

NEC 314.16 gives every wire a volume by its size, then counts everything in the box as a number of wires:

  • Each insulated wire that comes into the box counts once. Pigtails that start and end inside the box do not count.
  • All the ground wires together count as one wire of the largest ground. From the 2020 NEC, add a quarter for each ground beyond four.
  • Each device, a switch or receptacle on one strap, counts as two wires of the largest wire connected to it.
  • Internal cable clamps, however many, count as one wire of the largest in the box.
  • Each fixture stud or hickey counts as one of the largest wire.
Required volume = sum of (counted wires x volume per wire)

A single-gang box with three 12/2 cables feeding a receptacle: six 12 AWG wires (6), three grounds (1), the receptacle (2) and the clamps (1) make 10 wires of 12 AWG at 2.25 cu in: 22.5 cu in. A 4 x 1-1/2 in square box at 21.0 is too small; a 4 x 2-1/8 in at 30.3 works.

Plastic boxes are not in the table. Nonmetallic boxes are marked with their volume, often 18 to 22.5 cu in for a single gang, and that marking governs. Check it inside the box.

Questions

How many wires can go in a box?

It depends on the box volume and wire size. A 4 x 2-1/8 in square box holds 15 wires of 14 AWG or 13 of 12 AWG, before devices, clamps and grounds are counted. The calculator counts all of it.

How do I count box fill?

Count each wire entering the box as one, all grounds together as one, each switch or receptacle as two, and any internal clamps as one. Multiply by 2.00 cu in for 14 AWG or 2.25 for 12 AWG and compare with the box volume.

Do ground wires count in box fill?

Yes. All the equipment grounding conductors together count as one wire of the largest ground, and under the 2020 and 2023 NEC each ground beyond four adds a quarter more.

Do wire nuts count in box fill?

No. Wire connectors, splicing devices and pigtails that start and end in the box are not counted.

What is the volume of a 4 inch square box?

18.0 cu in at 1-1/4 in deep, 21.0 at 1-1/2 in and 30.3 at 2-1/8 in, by NEC Table 314.16(A). A plaster ring or extension adds the volume marked on it.