Electrical load calculator
Enter the floor area, appliances and heating and cooling equipment to get the calculated load and the service size, with every demand factor shown.
Inputs
Result
- General lighting, 3 VA/ft²
- 6,000 VA
- Small-appliance circuits
- 3,000 VA
- Laundry circuit
- 1,500 VA
- Appliances, nameplate
- 23,600 VA
- General load total
- 34,100 VA
- After demand factors
- 19,640 VA
- Heating or cooling
- 5,000 VA
- Calculated load
- 24,640 VA
Heating and cooling options, 220.82(C)
Only the largest of these is added to the general load.
| Option | Load, VA |
|---|---|
| Air conditioning at 100% | 5,000 |
| Heat pump, no supplemental heat, at 100% | 0 |
| Heat pump at 100% plus supplemental heat at 65% | 0 |
| Space heating, fewer than 4 units, at 65% | 0 |
| Thermal storage heating at 100% | 0 |
How it works
The optional method in NEC 220.82 applies to a single dwelling unit served by a 120/240 V or 208Y/120 V three-wire service or feeder of 100 A or more. It adds two parts.
General loads, 220.82(B)
- 3 VA per square foot for general lighting and receptacles
- 1,500 VA for each 20 A small-appliance circuit and each laundry circuit
- The nameplate rating of every appliance fastened in place or on a dedicated circuit: range, dryer, water heater, dishwasher, EV charger and so on
The first 10,000 VA counts at 100% and the rest at 40%.
Heating and air conditioning, 220.82(C)
Add only the largest of: air conditioning at 100%; a heat pump without supplemental heat at 100%; a heat pump compressor at 100% plus supplemental heat at 65%; electric space heating at 65% for fewer than four separately controlled units, or 40% for four or more; thermal storage heating at 100%.
When to use a different method
The standard method in Article 220, Part III often gives a different answer and is the one to use for services under 100 A. Adding load to an existing home has its own optional method in 220.83, and 220.87 lets you use a year of measured peak demand instead of a calculation. Your utility and inspector may also have their own requirements.
Questions
Do I need a 200 amp service?
Only if the calculated load is over 150 A. A 2,000 ft² home with a range, dryer, water heater, dishwasher and central air typically comes to about 100 A under the optional method; electric heat, a heat pump with strip heat or an EV charger are what usually push a home past 150 A.
Can I add an EV charger to a 100 amp panel?
Sometimes. Add the charger's nameplate VA here to see the new calculated load. For an existing home, 220.83 and 220.87 can give a more accurate answer, and a load management device can let a charger share capacity.
What is the difference between VA and watts?
For resistive loads such as heaters and ranges they are equal. For motors, VA is slightly higher than watts. Load calculations use VA from the nameplate: volts × amps.
Why does the calculator only add one heating or cooling load?
Heating and cooling rarely run at the same time, so 220.82(C) adds only the largest of the options rather than all of them.
Which NEC edition does this follow?
The 220.82 method, demand factors and 3 VA per square foot used here are as published in the 2017 through 2023 editions. Check which edition your jurisdiction has adopted.
What is the service demand of a 3-phase, 20 hp, 230 V HVAC unit?
About 21,512 VA. NEC Table 430.250 gives a full-load current of 54 A for a 20 hp three-phase motor at 230 V, and the NEC sizes motor loads from that table, not the nameplate (430.6(A)(1)). Three-phase VA = 54 A x 230 V x √3 = 21,512 VA; textbooks that round √3 to 1.732 get 21,511 VA. If it is the largest motor in a load calculation, 430.24 adds 25% of its current, taking it to 26,890 VA (26,889 with 1.732).
Sources
- NFPA 70, National Electrical Code (NEC). National Fire Protection Association. Free read-only access with a free NFPA account.
Codes are adopted and amended locally. Check the edition in force where you work.
More Electrical calculators
Voltage drop calculator
Drop in volts and percent for copper or aluminum, single-phase, three-phase or DC.
Conduit fill calculator
Fill percentage and the smallest EMT, rigid or PVC conduit for a mix of THHN conductors.
Recessed lighting calculator
How many can lights a room needs, the spacing, where each one goes from the wall, and whether that hits the light level the room wants.
Wire size & ampacity calculator
Conductor size and breaker from the load, with ambient correction and bundling adjustment applied.
Minimum circuit ampacity calculator
MCA, max breaker and wire size for an AC condenser, heat pump or air handler, from the nameplate amps.
Box fill calculator
Box fill volume by NEC 314.16 for any mix of wires, devices, clamps and grounds, and which boxes are big enough.
Watts to amps calculator
Convert watts to amps for DC, single-phase and three-phase power, with power factor and the breaker it needs.
Amps to watts calculator
Convert amps to watts, kilowatts and VA at any voltage, DC or AC, single- or three-phase.
kVA calculator
kVA to amps, amps to kVA and kW to kVA, single- or three-phase, with the next standard transformer size.
Generator sizing calculator
The generator size a house actually needs, counting one motor start at a time instead of all of them at once.
Breaker size calculator
The breaker a load or motor needs, with the 125% continuous rule, the motor tables and the wire that goes with it.
Electricity cost calculator
What an appliance or a whole list of them costs to run per hour, day, month and year, at your state’s average rate or your own.
EV charging cost calculator
What it costs to charge an electric car at home, at public chargers and at fast chargers, per mile and per month, compared with gas.
Space heater cost calculator
What a space heater costs to run per hour, day, month and winter, and how much electricity it really uses, at your state’s rate.