Conduit fill calculator

Add the conductors going into the raceway to get the fill percentage, the limit that applies, and the smallest trade size that fits.

NEC Chapter 9, Tables 1, 4 and 5THHN / THWN / THWN-2Note 7 round-up

Inputs

Conductors (THHN / THWN-2)
Include equipment grounding conductors. They count toward fill.

Result

Conduit fill
7.5% fill
Within the 40% limit for 3 conductors
Conductors
3
Conductor area
0.0399 in²
Conduit area (100%)
0.533 in²
Allowed at 40%
0.2132 in²

Smallest EMT that fits: 1 in (4.6%)

Maximum 12 AWG THHN conductors by trade size

For the conduit type selected and the first wire size in your list, all conductors the same size.

Trade sizeMax conductors
1 in26
2 in101
3 in266
4 in443
1/2 in9
3/4 in16
1-1/4 in45
1-1/2 in61
2-1/2 in176
3-1/2 in347

How many THHN wires fit in EMT

Maximum number of THHN / THWN-2 conductors of one size in each trade size of EMT, at the NEC Chapter 9 fill limits (53% for one wire, 31% for two, 40% for three or more) with the Note 7 round-up. These are the same counts as NEC Annex C, Table C.1. Ground wires count toward the total.

THHN wire1/2"3/4"1"1-1/4"1-1/2"2"
14 AWG1222356184138
12 AWG916264561101
10 AWG51016283863
8 AWG369162236
6 AWG147121626
4 AWG12471016
3 AWG1136813
2 AWG1135711
1 AWG111458
1/0 AWG011347

How many THHN wires fit in PVC Schedule 40

Same rules, using the smaller inside area of PVC Schedule 40 (Chapter 9, Table 4).

THHN wire1/2"3/4"1"1-1/4"1-1/2"2"
14 AWG1121346082135
12 AWG81525435999
10 AWG5915273762
8 AWG359162136
6 AWG146111526
4 AWG1147916
3 AWG1136813
2 AWG1135711
1 AWG011358
1/0 AWG011347

How many THHN wires fit in rigid metal conduit

THHN wire1/2"3/4"1"1-1/4"1-1/2"2"
14 AWG1322366385140
12 AWG916264662102
10 AWG61017293964
8 AWG369162237
6 AWG147121627
4 AWG12471016
3 AWG1136814
2 AWG1135711
1 AWG111458
1/0 AWG011347

How it works

Conduit fill compares the total cross-section of the conductors with the inside area of the raceway. The limits come from NEC Chapter 9, Table 1:

Number of conductorsMaximum fill
153%
231%
Over 240%

Conductor areas come from Chapter 9, Table 5, for THHN, THWN and THWN-2 insulation. Raceway areas come from Table 4 for the type and trade size you choose. When every conductor is the same size, Chapter 9, Note 7 allows the count to round up to the next whole number if the calculation lands at 0.8 or more, which is how the tables in Annex C are built.

What this calculator does not cover

  • Other insulation types, such as XHHW, RHW and compact conductors, have different areas.
  • Nipples of 24 in. or less may be filled to 60%, under Chapter 9, Note 4.
  • Cables, bare conductors and multiconductor assemblies are calculated differently.
  • Trade sizes 2-1/2 and 3-1/2 are listed for EMT only, until their published areas for rigid and PVC are confirmed.
Fill is not the only limit. More than three current-carrying conductors in one raceway reduces their ampacity under 310.15(C)(1), and the total bends between pull points cannot exceed 360°.

Questions

How many 12 AWG wires fit in 1/2 inch EMT?

Nine 12 AWG THHN conductors fit in 1/2 in. EMT at 40% fill. In 3/4 in. EMT the limit is 16, and in 1 in. EMT it is 26.

Do ground wires count toward conduit fill?

Yes. Equipment grounding and bonding conductors count toward fill and are included in the conductor count.

Why is the limit 31% for two conductors?

Two round conductors can jam against each other inside a raceway more easily than one or three, so Table 1 sets a lower limit of 31% for exactly two.

How many 14 AWG wires fit in 3/4 EMT?

Twenty-two 14 AWG THHN conductors. The calculation gives 21.98, and Chapter 9, Note 7 allows rounding up when the decimal is 0.8 or more.

Can I mix wire sizes?

Yes. Add a row for each size. With mixed sizes the total area must stay within the limit, and the Note 7 round-up does not apply.

How many 12 AWG THHN wires fit in 1 inch EMT?

Twenty-six 12 AWG THHN conductors fit in 1 in. EMT at 40% fill. In 3/4 in. EMT it is 16, and in 1-1/4 in. EMT 45. In 1 in. PVC Schedule 40, 25.

How many 10 AWG THHN wires fit in 3/4 EMT?

Ten 10 AWG THHN conductors fit in 3/4 in. EMT. In 1/2 in. EMT it is 5, and in 1 in. EMT 16.

How many 8 AWG THHN wires fit in 3/4 EMT?

Six 8 AWG THHN conductors fit in 3/4 in. EMT. In 1 in. EMT it is 9, and in 1/2 in. EMT 3.

How many 8 AWG THHN wires fit in 1 inch EMT?

Nine 8 AWG THHN conductors fit in 1 in. EMT. In 1-1/4 in. EMT it is 16.

How many 6 AWG wires fit in 1/2 EMT?

Only 1. Two 6 AWG THHN conductors fill 33% of 1/2 in. EMT, over the 31% limit for exactly two conductors. In 3/4 in. EMT, 4 fit, and in 1 in. EMT 7.

Sources

Codes are adopted and amended locally. Check the edition in force where you work.

More Electrical calculators

Voltage drop calculator

Drop in volts and percent for copper or aluminum, single-phase, three-phase or DC.

Recessed lighting calculator

How many can lights a room needs, the spacing, where each one goes from the wall, and whether that hits the light level the room wants.

Electrical load calculator

Dwelling service size by the NEC 220.82 optional method, with every demand factor shown.

Wire size & ampacity calculator

Conductor size and breaker from the load, with ambient correction and bundling adjustment applied.

Minimum circuit ampacity calculator

MCA, max breaker and wire size for an AC condenser, heat pump or air handler, from the nameplate amps.

Box fill calculator

Box fill volume by NEC 314.16 for any mix of wires, devices, clamps and grounds, and which boxes are big enough.

Watts to amps calculator

Convert watts to amps for DC, single-phase and three-phase power, with power factor and the breaker it needs.

Amps to watts calculator

Convert amps to watts, kilowatts and VA at any voltage, DC or AC, single- or three-phase.

kVA calculator

kVA to amps, amps to kVA and kW to kVA, single- or three-phase, with the next standard transformer size.

Generator sizing calculator

The generator size a house actually needs, counting one motor start at a time instead of all of them at once.

Breaker size calculator

The breaker a load or motor needs, with the 125% continuous rule, the motor tables and the wire that goes with it.

Electricity cost calculator

What an appliance or a whole list of them costs to run per hour, day, month and year, at your state’s average rate or your own.

EV charging cost calculator

What it costs to charge an electric car at home, at public chargers and at fast chargers, per mile and per month, compared with gas.

Space heater cost calculator

What a space heater costs to run per hour, day, month and winter, and how much electricity it really uses, at your state’s rate.

Other trades