CFM airflow calculator
Three ways to get an airflow figure: from the system's tonnage, from air changes per hour for a room, or from the ASHRAE 62.2 whole-house ventilation rate.
Inputs
Result
- Capacity
- 36,000 BTU/h
- Airflow per ton
- 400 cfm
- Expected drop across the coil, at 70% sensible
- 19.4 °F
Airflow split between rooms
| Room | Area, ft² | Share | Airflow, cfm |
|---|---|---|---|
| Living room | 400 | 40.0% | 480 |
| Kitchen | 200 | 20.0% | 240 |
| Primary bedroom | 250 | 25.0% | 300 |
| Bedroom 2 | 150 | 15.0% | 180 |
System airflow, from tonnage
Cooling equipment is designed around a nominal 400 cfm per ton, with 350 to 450 the range in normal use. At 400 cfm per ton and typical return air of 80 °F at 50% relative humidity, a coil does roughly 70% sensible cooling and 30% latent, on about a 20 °F temperature drop.
Moving less air per ton makes the coil colder, which removes more moisture but risks drafts and a frozen coil. Moving more air per ton does the opposite: better sensible cooling, less dehumidification, and larger ducts to carry it. In humid climates technicians often aim nearer 350; in dry climates nearer 450.
Airflow follows the nominal tonnage, so an air handler is normally matched to the condenser it runs with: a 4 ton system wants about 1,600 cfm across the coil and a 5 ton system about 2,000 cfm. The blower has to deliver that against the static pressure of the duct it is connected to, which is a separate question from whether it is rated for it.
Tons to CFM chart
| System | Capacity, BTU/h | 350 cfm/ton | 400 cfm/ton | 450 cfm/ton |
|---|---|---|---|---|
| 1.5 ton | 18,000 | 525 | 600 | 675 |
| 2 ton | 24,000 | 700 | 800 | 900 |
| 2.5 ton | 30,000 | 875 | 1,000 | 1,125 |
| 3 ton | 36,000 | 1,050 | 1,200 | 1,350 |
| 3.5 ton | 42,000 | 1,225 | 1,400 | 1,575 |
| 4 ton | 48,000 | 1,400 | 1,600 | 1,800 |
| 5 ton | 60,000 | 1,750 | 2,000 | 2,250 |
The 400 cfm per ton column is the nominal design figure and the one to use unless you have a reason not to. One ton is 12,000 BTU/h, which is where the capacity column comes from.
Room airflow, from air changes (air exchange rate)
Air changes per hour and air exchange rate are the same measurement under two names: how many times the air in a room is replaced in an hour. Equipment data sheets and ventilation standards say air changes; a lot of people searching for it say air exchange. Either way the arithmetic is the same.
Air changes per hour asks how many times the air in a room is replaced each hour. It is the usual method for ventilation and exhaust, rather than for sizing cooling supply.
A 300 ft² room with an 8 ft ceiling holds 2,400 ft³. At 2 air changes an hour that is 80 cfm.
Whole-house ventilation, ASHRAE 62.2
ASHRAE Standard 62.2 sets the mechanical ventilation rate for a dwelling:
Occupancy is assumed from the bedroom count rather than asked for: two people in the main bedroom and one in each other bedroom, which works out as bedrooms plus one. That whole-dwelling rate is only half of what the standard asks for: it also sets local exhaust for kitchens and bathrooms, on top of it rather than instead of it.
Local exhaust for kitchens and bathrooms
ASHRAE 62.2 wants the air removed at the source in the two rooms that produce the most moisture and the most cooking by-products. There are two ways to meet it, and you pick one per room: a fan that runs only when the room is in use, at the higher intermittent rate, or one that runs continuously at a much lower rate.
| Room | Intermittent | Continuous |
|---|---|---|
| Bathroom, each one | 50 cfm | 20 cfm |
| Kitchen, vented range hood | 100 cfm | 5 ACH |
| Kitchen, any other exhaust fan | 300 cfm | 5 ACH |
The kitchen is the one row that is not a fixed number. A range hood ducted to the outside clears cooking by-products where they are produced, so 100 cfm is enough; an exhaust fan somewhere else in the room has to move the whole room's air to do the same job, which is why it jumps to 300 cfm. Running continuously, the kitchen requirement is 5 air changes an hour on the kitchen's own volume — a 180 ft² kitchen with an 8 ft ceiling holds 1,440 ft³, so 1,440 × 5 ÷ 60 = 120 cfm.
A bathroom fan is sized by this table, not by the air changes calculator above. The air changes method is the general way to get an airflow figure for any space; ASHRAE 62.2 is what a residential inspector measures against.
Once you have the airflow, the duct size calculator turns it into duct sizes, and the static pressure calculator tells you whether the system can actually move it.
Questions
How many CFM per ton of air conditioning?
400 cfm per ton is the nominal design figure, with 350 to 450 the normal range. A 3 ton system is therefore about 1,200 cfm.
How many CFM is a 4 ton air handler?
About 1,600 cfm, from 4 tons at the nominal 400 cfm per ton. The usable range is 1,400 to 1,800 cfm, because 350 to 450 cfm per ton are both normal. A 5 ton air handler is about 2,000 cfm on the same basis, and a 3 ton about 1,200 cfm.
How do I convert CFM to BTU?
There is no direct conversion, which is the part most calculators skip. Airflow on its own does not tell you the heat being moved: you also need the temperature difference across the coil. The sensible heat equation is BTU/h = 1.08 × cfm × ΔT, where 1.08 carries the density and specific heat of standard air. So 1,200 cfm across a 20 °F drop is 1.08 × 1,200 × 20 = 25,920 BTU/h of sensible cooling. Going the other way, cfm = BTU/h ÷ (1.08 × ΔT). If what you actually want is the airflow a given tonnage needs, use the chart above instead — that is the 400 cfm per ton rule, and it is a different question.
What is an air exchange rate, and how do I calculate CFM from it?
Air exchange rate is another name for air changes per hour (ACH): how many times a room's entire volume of air is replaced each hour. To turn it into airflow, multiply the room's volume by the rate and divide by 60, because cfm is per minute. A 300 ft² room with 8 ft ceilings is 2,400 ft³; at 2 air changes an hour that is 2,400 × 2 ÷ 60 = 80 cfm.
How many air changes per hour does a room need?
It depends on the room. Living spaces and bedrooms are usually designed around 2 to 4 air changes an hour, kitchens and bathrooms far more because the air needs removing rather than recirculating, and workshops and commercial spaces have their own figures. The calculator carries a rate for each space type and lets you override it.
How do I calculate CFM for a room?
Multiply the floor area by the ceiling height to get the volume, multiply by the air changes per hour you want, then divide by 60. A 300 ft² room with 8 ft ceilings at 2 ACH needs 80 cfm.
What is a good CFM per square foot?
For residential cooling supply, roughly 0.5 to 1 cfm per square foot falls out of the 400 cfm per ton figure once a system is sized. Ventilation is a different calculation: ASHRAE 62.2 uses 0.03 cfm per square foot plus 7.5 cfm per occupant.
Why is my temperature drop not 20 degrees?
Temperature drop and airflow move together. A drop much above 20 °F usually means too little airflow, from a dirty filter, a restricted return or a slow blower. A drop well below it usually means too much airflow or a refrigerant problem.
How much ventilation does ASHRAE 62.2 require?
0.03 cfm per square foot of floor area plus 7.5 cfm per occupant, with occupancy counted as the number of bedrooms plus one. A 2,000 ft² home with 3 bedrooms needs 90 cfm continuously.
Sources
- ASHRAE Standard 62.2, Ventilation for Acceptable Indoor Air Quality in Residential Buildings. ASHRAE.
- ACCA Manual D: Residential Duct Design. Air Conditioning Contractors of America.
More HVAC calculators
Duct size calculator
Round and rectangular duct sizes from airflow and friction rate, with a CFM chart for every size.
Static pressure calculator
Total external static pressure from your readings, plus the friction rate for duct sizing.
AC tonnage calculator
Cooling capacity estimate by floor area and climate zone, with an honest check against real load calculations.
Furnace size calculator
Furnace BTU from floor area, climate zone and construction, converted to input by AFUE and checked against the ACCA Manual S range.
Heat pump size calculator
Heat pump tons from floor area and climate zone within the ACCA Manual S limits, with backup heat and balance point from your heat loss.
Mini split size calculator
Mini split BTU for each room by the ENERGY STAR sizing chart, the indoor head for each, and the outdoor unit for a multi-zone system.
BTU calculator
BTU to cool or heat a room by its size, sun, people and kitchen, the AC size to buy, and the same load in watts, kW and tons.
Flex duct CFM chart calculator
How much air each flex size really carries, stretched and compressed, against sheet metal.