RoughInSizing calculators for the trades

Wire size calculator

Enter the load and the conditions in the raceway to get the conductor size, the breaker, and every derating step that led to it.

NEC Table 310.16310.15(B)(1) and 310.15(C)(1)110.14(C) terminations240.6(A)

Inputs

A
Load typeAdds the 125% factor.
Conductor
Insulation rating
°C
30 °C is the table basis. Attics and rooftops run hotter.
in raceway
Neutrals on a balanced 3-wire circuit and grounds do not count.
Equipment termination rating

Result

Minimum conductor for 60 A
4AWG Cu
60 A overcurrent device
Limited by the 60 °C termination column, not by derating
Base ampacity, 90 °C column
95 A
Ambient correction at 30 °C
× 1.00
Adjustment, 3 current-carrying
× 1.00
After derating
95.0 A
Termination limit, 60 °C column
70 A
Usable ampacity
70.0 A

Every size under these conditions

Base ampacity from your chosen column, then corrected and adjusted, then capped by the termination column.

SizeBase, AAfter deratingTermination limitUsable, A
14 AWG2525.01515.0
12 AWG3030.02020.0
10 AWG4040.03030.0
8 AWG5555.04040.0
6 AWG7575.05555.0
4 AWG9595.07070.0
3 AWG115115.08585.0
2 AWG130130.09595.0
1 AWG145145.0110110.0
1/0 AWG170170.0125125.0
2/0 AWG195195.0145145.0
3/0 AWG225225.0165165.0
4/0 AWG260260.0195195.0
250 kcmil290290.0215215.0
300 kcmil320320.0240240.0
350 kcmil350350.0260260.0

The three limits that decide a wire size

A conductor has to pass all three, and the smallest answer wins.

  1. Ampacity after derating. Start in the column for the conductor's insulation rating in Table 310.16, then multiply by the ambient correction from Table 310.15(B)(1) and the adjustment factor from Table 310.15(C)(1).
  2. Termination temperature, 110.14(C). Equipment terminations are usually rated 60 °C up to 100 A and 75 °C above that, unless the equipment is marked otherwise. You may start from the 90 °C column for derating, but the final ampacity cannot exceed the termination column's value.
  3. Overcurrent protection, 240.4. The device protects the conductor. 240.4(D) caps small conductors regardless of ampacity: 15 A for 14 AWG copper, 20 A for 12 AWG, 30 A for 10 AWG.
Usable ampacity = min( base × ambient correction × bundling adjustment , termination column )

What counts as a current-carrying conductor

Ungrounded conductors always count. A neutral counts only when it carries current in normal operation, so the neutral of a balanced 3-wire circuit does not, while the neutral of a circuit supplying nonlinear loads does. Equipment grounding conductors never count. The adjustment factor only applies when more than three current-carrying conductors run together for more than 24 inches.

Wire size by amps: 15 to 100 amp circuits

The smallest wire for each breaker size with no derating: NEC Table 310.16, with NM cable taken from the 60 °C column, THHN and aluminum from the 75 °C column, and the 240.4(D) small-conductor limits applied. Hot attics, bundled cables and long runs can all push it up a size, which the calculator above works out.

CircuitCopper NM (Romex)Copper THHNAluminum
15 A14 AWG14 AWG12 AWG
20 A12 AWG12 AWG10 AWG
25 A10 AWG10 AWG10 AWG
30 A10 AWG10 AWG8 AWG
35 A8 AWG8 AWG8 AWG
40 A8 AWG8 AWG8 AWG
45 A6 AWG8 AWG6 AWG
50 A6 AWG8 AWG6 AWG
60 A4 AWG6 AWG4 AWG
70 A4 AWG4 AWG3 AWG
80 A3 AWG4 AWG2 AWG
90 A2 AWG3 AWG2 AWG
100 A1 AWG3 AWG1 AWG

For runs over about 100 ft, check the voltage drop; for the breaker a particular appliance needs, use the breaker size calculator.

This is a general calculation. It does not apply NEC 310.12, which lets dwelling service and feeder conductors be sized at 83% of the service rating, nor motor circuits under Article 430, which are sized from table values rather than the nameplate. Both give smaller conductors than the general method.

Questions

What size wire do I need for a 50 amp circuit?

6 AWG copper NM cable, or 8 AWG copper THHN where the breaker and equipment are rated for 75 °C, or 6 AWG aluminum. That assumes no derating; a long run, a hot attic or several cables bundled together can need the next size up. Ranges, EV chargers, hot tubs and RV outlets on 50 A circuits are usually wired in 6 AWG copper.

What size wire for a 30 amp breaker?

10 AWG copper, in NM cable or THHN. NEC 240.4(D) allows 10 AWG copper on up to 30 A, so it is the standard choice for 30 A dryers and water heaters. In aluminum, 8 AWG.

What size wire for 40 amps?

8 AWG copper NM cable or 8 AWG copper THHN, and 8 AWG aluminum.

What size wire do I need for 100 amps?

With 75 °C terminations and no derating, 3 AWG copper or 1/0 aluminum carries 100 A. Many jurisdictions see 4 AWG copper on a 100 A dwelling feeder, which comes from the separate 83% allowance in NEC 310.12 rather than from this general calculation.

Can I use the 90 °C column?

For derating, yes, if the conductor is rated 90 °C such as THHN. The final ampacity still cannot exceed the 60 °C or 75 °C termination column, because the connection points are the weak link, not the insulation.

When does the 125% continuous factor apply?

When the load runs for three hours or more without interruption. Tick the box and the calculator sizes the conductor and device for 125% of the load.

Do ground wires count toward the conductor count?

No. Equipment grounding conductors are not current-carrying under normal conditions, so they are excluded from the adjustment factor, though they still count toward conduit fill.

Why does my 12 AWG only get a 20 amp breaker?

NEC 240.4(D) limits overcurrent protection on small conductors regardless of their ampacity: 15 A on 14 AWG copper, 20 A on 12 AWG and 30 A on 10 AWG.

Sources

Codes are adopted and amended locally. Check the edition in force where you work.

More Electrical calculators

Voltage drop calculator

Drop in volts and percent for copper or aluminum, single-phase, three-phase or DC.

Conduit fill calculator

Fill percentage and the smallest EMT, rigid or PVC conduit for a mix of THHN conductors.

Recessed lighting calculator

How many can lights a room needs, the spacing, where each one goes from the wall, and whether that hits the light level the room wants.

Electrical load calculator

Dwelling service size by the NEC 220.82 optional method, with every demand factor shown.

Minimum circuit ampacity calculator

MCA, max breaker and wire size for an AC condenser, heat pump or air handler, from the nameplate amps.

Box fill calculator

Box fill volume by NEC 314.16 for any mix of wires, devices, clamps and grounds, and which boxes are big enough.

Watts to amps calculator

Convert watts to amps for DC, single-phase and three-phase power, with power factor and the breaker it needs.

Amps to watts calculator

Convert amps to watts, kilowatts and VA at any voltage, DC or AC, single- or three-phase.

kVA calculator

kVA to amps, amps to kVA and kW to kVA, single- or three-phase, with the next standard transformer size.

Generator sizing calculator

The generator size a house actually needs, counting one motor start at a time instead of all of them at once.

Breaker size calculator

The breaker a load or motor needs, with the 125% continuous rule, the motor tables and the wire that goes with it.

Electricity cost calculator

What an appliance or a whole list of them costs to run per hour, day, month and year, at your state’s average rate or your own.

EV charging cost calculator

What it costs to charge an electric car at home, at public chargers and at fast chargers, per mile and per month, compared with gas.

Space heater cost calculator

What a space heater costs to run per hour, day, month and winter, and how much electricity it really uses, at your state’s rate.

Other trades