RoughInSizing calculators for the trades

Wire size calculator

Enter the load and the conditions in the raceway to get the conductor size, the breaker, and every derating step that led to it.

NEC Table 310.16310.15(B)(1) and 310.15(C)(1)110.14(C) terminations240.6(A)

Inputs

A
Load typeAdds the 125% factor.
Conductor
Insulation rating
°C
30 °C is the table basis. Attics and rooftops run hotter.
in raceway
Neutrals on a balanced 3-wire circuit and grounds do not count.
Equipment termination rating

Result

Minimum conductor for — A
—

Every size under these conditions

Base ampacity from your chosen column, then corrected and adjusted, then capped by the termination column.

SizeBase, AAfter deratingTermination limitUsable, A

The three limits that decide a wire size

A conductor has to pass all three, and the smallest answer wins.

  1. Ampacity after derating. Start in the column for the conductor's insulation rating in Table 310.16, then multiply by the ambient correction from Table 310.15(B)(1) and the adjustment factor from Table 310.15(C)(1).
  2. Termination temperature, 110.14(C). Equipment terminations are usually rated 60 °C up to 100 A and 75 °C above that, unless the equipment is marked otherwise. You may start from the 90 °C column for derating, but the final ampacity cannot exceed the termination column's value.
  3. Overcurrent protection, 240.4. The device protects the conductor. 240.4(D) caps small conductors regardless of ampacity: 15 A for 14 AWG copper, 20 A for 12 AWG, 30 A for 10 AWG.
Usable ampacity = min( base × ambient correction × bundling adjustment , termination column )

What counts as a current-carrying conductor

Ungrounded conductors always count. A neutral counts only when it carries current in normal operation, so the neutral of a balanced 3-wire circuit does not, while the neutral of a circuit supplying nonlinear loads does. Equipment grounding conductors never count. The adjustment factor only applies when more than three current-carrying conductors run together for more than 24 inches.

This is a general calculation. It does not apply NEC 310.12, which lets dwelling service and feeder conductors be sized at 83% of the service rating, nor motor circuits under Article 430, which are sized from table values rather than the nameplate. Both give smaller conductors than the general method.

Questions

What size wire do I need for 100 amps?

With 75 °C terminations and no derating, 3 AWG copper or 1/0 aluminum carries 100 A. Many jurisdictions see 4 AWG copper on a 100 A dwelling feeder, which comes from the separate 83% allowance in NEC 310.12 rather than from this general calculation.

Can I use the 90 °C column?

For derating, yes, if the conductor is rated 90 °C such as THHN. The final ampacity still cannot exceed the 60 °C or 75 °C termination column, because the connection points are the weak link, not the insulation.

When does the 125% continuous factor apply?

When the load runs for three hours or more without interruption. Tick the box and the calculator sizes the conductor and device for 125% of the load.

Do ground wires count toward the conductor count?

No. Equipment grounding conductors are not current-carrying under normal conditions, so they are excluded from the adjustment factor, though they still count toward conduit fill.

Why does my 12 AWG only get a 20 amp breaker?

NEC 240.4(D) limits overcurrent protection on small conductors regardless of their ampacity: 15 A on 14 AWG copper, 20 A on 12 AWG and 30 A on 10 AWG.

More Electrical calculators

Other trades