Breaker size calculator
Enter the load in watts or amps, or pick a motor. You get the breaker size, the wire that goes with it, and how much of the breaker the load uses, by the NEC rules for continuous loads and motors.
Inputs
Result
Breaker sizes for common loads
Single-phase, by the rules on this page. Continuous loads are sized at 125%.
| Load | Amps | Continuous | Breaker | NM cable | THHN |
|---|---|---|---|---|---|
| Space heater, 1,500 W at 120 V | 12.5 A | Yes | 20 A | 12 AWG | 12 AWG |
| Baseboard heater, 2,000 W at 240 V | 8.3 A | Yes | 15 A | 14 AWG | 14 AWG |
| Electric water heater, 4,500 W at 240 V | 18.8 A | Yes | 25 A | 10 AWG | 10 AWG |
| EV charger, 48 A at 240 V | 48.0 A | Yes | 60 A | 4 AWG | 6 AWG |
| EV charger, 32 A at 240 V | 32.0 A | Yes | 40 A | 8 AWG | 8 AWG |
| Electric dryer, 5,600 W at 240 V | 23.3 A | No | 25 A | 10 AWG | 10 AWG |
| Microwave, 1,200 W at 120 V | 10.0 A | No | 15 A | 14 AWG | 14 AWG |
| Dishwasher, 1,800 W at 120 V | 15.0 A | No | 15 A | 14 AWG | 14 AWG |
| Hot tub heater, 5,500 W at 240 V | 22.9 A | Yes | 30 A | 10 AWG | 10 AWG |
| Shop heater, 10 kW at 240 V | 41.7 A | Yes | 60 A | 6 AWG | 6 AWG |
How breaker size is worked out
The 125% rule (NEC 210.20(A)) is why a 1,500 W heater, which draws 12.5 A, needs a 20 A breaker and not a 15. Standard breakers are only rated to carry 80% of their rating continuously, and 125% is the same thing turned around. Space heaters, baseboard heat, water heaters, EV chargers, pool and hot tub heaters and lighting left on all evening are all continuous loads.
The wire has to match the breaker
The breaker protects the wire, not the appliance. Once the breaker size is set, the wire must be rated for it: 14 AWG copper for 15 A, 12 AWG for 20 A and 10 AWG for 30 A (NEC 240.4(D)), whatever the ampacity table says. Above 30 A the wire follows its ampacity, and NM cable must be sized from the 60 °C column. Where a wire’s ampacity falls between two breaker sizes, NEC 240.4(B) allows the next breaker up, as long as the wire still covers the load: that is how 6 AWG NM, rated 55 A, can go on a 60 A breaker.
Motors follow different rules
A motor draws several times its running current for a moment as it starts, so its breaker is sized to ride through that, and a separate overload device protects it while running. The NEC uses its own full-load current tables, not the nameplate: Table 430.248 for single-phase motors and 430.250 for three-phase. An inverse-time breaker can be up to 250% of that current, rounded up to the next standard size, and the wire is sized at 125%. Because of that, a motor circuit can legally have a 30 A breaker on 14 AWG wire. If the motor still trips the breaker on start, NEC 430.52 allows up to 400% for motors drawing 100 A or less.
Air conditioners and heat pumps use the minimum circuit ampacity and maximum breaker printed on their nameplate instead. Use the minimum circuit ampacity calculator for those.
How many watts can a breaker take?
Continuous loads are limited to 80% of the breaker; anything else can use the full rating.
| Breaker | 120 V, continuous | 120 V, max | 240 V, continuous | 240 V, max |
|---|---|---|---|---|
| 15 A | 1,440 W | 1,800 W | 2,880 W | 3,600 W |
| 20 A | 1,920 W | 2,400 W | 3,840 W | 4,800 W |
| 25 A | 2,400 W | 3,000 W | 4,800 W | 6,000 W |
| 30 A | 2,880 W | 3,600 W | 5,760 W | 7,200 W |
| 40 A | 3,840 W | 4,800 W | 7,680 W | 9,600 W |
| 50 A | 4,800 W | 6,000 W | 9,600 W | 12,000 W |
| 60 A | 5,760 W | 7,200 W | 11,520 W | 14,400 W |
| 70 A | 6,720 W | 8,400 W | 13,440 W | 16,800 W |
| 80 A | 7,680 W | 9,600 W | 15,360 W | 19,200 W |
| 100 A | 9,600 W | 12,000 W | 19,200 W | 24,000 W |
Wire size for each breaker
The smallest wire whose ampacity covers the full breaker rating, by NEC Table 310.16 and 240.4(D).
| Breaker | Copper NM, 60 °C | Copper THHN, 75 °C | Aluminum, 75 °C |
|---|---|---|---|
| 15 A | 14 AWG | 14 AWG | 12 AWG |
| 20 A | 12 AWG | 12 AWG | 10 AWG |
| 25 A | 10 AWG | 10 AWG | 10 AWG |
| 30 A | 10 AWG | 10 AWG | 8 AWG |
| 40 A | 8 AWG | 8 AWG | 8 AWG |
| 50 A | 6 AWG | 8 AWG | 6 AWG |
| 60 A | 4 AWG | 6 AWG | 4 AWG |
| 70 A | 4 AWG | 4 AWG | 3 AWG |
| 80 A | 3 AWG | 4 AWG | 2 AWG |
| 90 A | 2 AWG | 3 AWG | 2 AWG |
| 100 A | 1 AWG | 3 AWG | 1 AWG |
| 125 A | 1/0 AWG | 1 AWG | 2/0 AWG |
| 150 A | 3/0 AWG | 1/0 AWG | 3/0 AWG |
| 200 A | 250 kcmil | 3/0 AWG | 250 kcmil |
Motor breaker chart
Single-phase motors, NEC Table 430.248 full-load current, inverse-time breaker at 250% rounded up, copper THHN at 125%.
| Motor | 115 V FLC | Breaker | Wire | 230 V FLC | Breaker | Wire |
|---|---|---|---|---|---|---|
| 1/6 hp | 4.4 A | 15 A | 14 AWG | 2.2 A | 15 A | 14 AWG |
| 1/4 hp | 5.8 A | 15 A | 14 AWG | 2.9 A | 15 A | 14 AWG |
| 1/3 hp | 7.2 A | 20 A | 14 AWG | 3.6 A | 15 A | 14 AWG |
| 1/2 hp | 9.8 A | 25 A | 14 AWG | 4.9 A | 15 A | 14 AWG |
| 3/4 hp | 13.8 A | 35 A | 14 AWG | 6.9 A | 20 A | 14 AWG |
| 1 hp | 16 A | 40 A | 14 AWG | 8 A | 20 A | 14 AWG |
| 1-1/2 hp | 20 A | 50 A | 12 AWG | 10 A | 25 A | 14 AWG |
| 2 hp | 24 A | 60 A | 10 AWG | 12 A | 30 A | 14 AWG |
| 3 hp | 34 A | 90 A | 8 AWG | 17 A | 45 A | 12 AWG |
| 5 hp | 56 A | 150 A | 4 AWG | 28 A | 70 A | 10 AWG |
| 7-1/2 hp | 80 A | 200 A | 3 AWG | 40 A | 100 A | 8 AWG |
| 10 hp | 100 A | 250 A | 1 AWG | 50 A | 125 A | 6 AWG |
Three-phase motors, NEC Table 430.250.
| Motor | 208 V FLC | Breaker | Wire | 460 V FLC | Breaker | Wire |
|---|---|---|---|---|---|---|
| 1/2 hp | 2.4 A | 15 A | 14 AWG | 1.1 A | 15 A | 14 AWG |
| 3/4 hp | 3.5 A | 15 A | 14 AWG | 1.6 A | 15 A | 14 AWG |
| 1 hp | 4.6 A | 15 A | 14 AWG | 2.1 A | 15 A | 14 AWG |
| 1-1/2 hp | 6.6 A | 20 A | 14 AWG | 3 A | 15 A | 14 AWG |
| 2 hp | 7.5 A | 20 A | 14 AWG | 3.4 A | 15 A | 14 AWG |
| 3 hp | 10.6 A | 30 A | 14 AWG | 4.8 A | 15 A | 14 AWG |
| 5 hp | 16.7 A | 45 A | 12 AWG | 7.6 A | 20 A | 14 AWG |
| 7-1/2 hp | 24.2 A | 70 A | 10 AWG | 11 A | 30 A | 14 AWG |
| 10 hp | 30.8 A | 80 A | 8 AWG | 14 A | 35 A | 14 AWG |
| 15 hp | 46.2 A | 125 A | 6 AWG | 21 A | 60 A | 10 AWG |
| 20 hp | 59.4 A | 150 A | 4 AWG | 27 A | 70 A | 10 AWG |
| 25 hp | 74.8 A | 200 A | 3 AWG | 34 A | 90 A | 8 AWG |
Questions
How do I calculate what size breaker I need?
Work out the amps (watts divided by volts), multiply by 1.25 if the load runs for three hours or more, and round up to the next standard breaker size. A 1,500 W heater at 120 V draws 12.5 A; times 1.25 is 15.6 A, so it needs a 20 A breaker on 12 AWG copper wire.
What is the 80% rule for breakers?
A standard breaker can carry only 80% of its rating continuously, meaning for three hours or more. That is the same as sizing the breaker at 125% of a continuous load. A 20 A breaker can carry 16 A continuously, which is 1,920 W at 120 V.
What size breaker do I need for a 48 amp EV charger?
A 60 A breaker. EV chargers are continuous loads, so 48 A × 1.25 = 60 A. With copper THHN that needs 6 AWG; with NM cable, 4 AWG.
What size breaker for a 4,500 watt water heater?
4,500 W at 240 V is 18.75 A. Water heaters count as continuous loads, so × 1.25 = 23.4 A, which rounds up to a 25 A breaker on 10 AWG copper. Many installers use 30 A on 10 AWG, which is also allowed.
How many amps can a 20 amp breaker handle?
20 A for short loads, and 16 A for loads that run three hours or more. At 120 V that is 2,400 W and 1,920 W.
What size breaker for a 2 hp motor?
For a 2 hp single-phase motor at 230 V, NEC Table 430.248 gives 12 A full-load current. 250% of that is 30 A, so a 30 A inverse-time breaker, with 14 AWG copper sized at 125% (15 A). At 115 V it is 24 A and a 60 A breaker on 10 AWG. The motor also needs its own overload protection.
Can I put a 30 amp breaker on 12 gauge wire?
Not for a normal circuit: 12 AWG copper is limited to a 20 A breaker by NEC 240.4(D). The exceptions are motor and air-conditioner circuits, where the code sizes the breaker to let the motor start and protects the wire with a separate overload, so the nameplate’s maximum breaker can exceed the usual limit.
More Electrical calculators
Voltage drop calculator
Drop in volts and percent for copper or aluminum, single-phase, three-phase or DC.
Conduit fill calculator
Fill percentage and the smallest EMT, rigid or PVC conduit for a mix of THHN conductors.
Electrical load calculator
Dwelling service size by the NEC 220.82 optional method, with every demand factor shown.
Wire size & ampacity calculator
Conductor size and breaker from the load, with ambient correction and bundling adjustment applied.
Minimum circuit ampacity calculator
MCA, max breaker and wire size for an AC condenser, heat pump or air handler, from the nameplate amps.
Box fill calculator
Box fill volume by NEC 314.16 for any mix of wires, devices, clamps and grounds, and which boxes are big enough.
Watts to amps calculator
Convert watts to amps for DC, single-phase and three-phase power, with power factor and the breaker it needs.
Amps to watts calculator
Convert amps to watts, kilowatts and VA at any voltage, DC or AC, single- or three-phase.
kVA calculator
kVA to amps, amps to kVA and kW to kVA, single- or three-phase, with the next standard transformer size.
Generator sizing calculator
The generator size a house actually needs, counting one motor start at a time instead of all of them at once.
Electricity cost calculator
What an appliance or a whole list of them costs to run per hour, day, month and year, at your state’s average rate or your own.
EV charging cost calculator
What it costs to charge an electric car at home, at public chargers and at fast chargers, per mile and per month, compared with gas.
Space heater cost calculator
What a space heater costs to run per hour, day, month and winter, and how much electricity it really uses, at your state’s rate.