Voltage drop calculator
Enter the circuit and conductor to get the voltage drop in volts and percent, the voltage at the load, and the smallest wire size that meets your target.
Inputs
Result
- Voltage drop
- 7.92 V
- Voltage at load
- 112.1 V
- Ampacity, 75 °C column
- 25 A
- Max overcurrent device, 240.4(D)
- 20 A
Smallest copper size for ≤ 3%: 8 AWG (2.59%)
Voltage drop for every wire size
Same circuit, same length, each conductor size. Ampacity is the 75 °C column of Table 310.16 before any correction or adjustment.
| Size | Drop, V | Drop, % | Ampacity, A |
|---|---|---|---|
| 14 AWG | 12.56 | 10.47% | 20 |
| 12 AWG | 7.92 | 6.60% | 25 |
| 10 AWG | 4.96 | 4.13% | 35 |
| 8 AWG | 3.11 | 2.59% | 50 |
| 6 AWG | 1.96 | 1.64% | 65 |
| 4 AWG | 1.23 | 1.03% | 85 |
| 3 AWG | 0.98 | 0.82% | 100 |
| 2 AWG | 0.78 | 0.65% | 115 |
| 1 AWG | 0.62 | 0.51% | 130 |
| 1/0 AWG | 0.49 | 0.41% | 150 |
| 2/0 AWG | 0.39 | 0.32% | 175 |
| 3/0 AWG | 0.31 | 0.26% | 200 |
| 4/0 AWG | 0.24 | 0.20% | 230 |
| 250 kcmil | 0.21 | 0.17% | 255 |
| 300 kcmil | 0.17 | 0.14% | 285 |
| 350 kcmil | 0.15 | 0.12% | 310 |
| 400 kcmil | 0.13 | 0.11% | 335 |
| 500 kcmil | 0.10 | 0.09% | 380 |
| 600 kcmil | 0.09 | 0.07% | 420 |
| 700 kcmil | 0.07 | 0.06% | 460 |
| 750 kcmil | 0.07 | 0.06% | 475 |
| 800 kcmil | 0.06 | 0.05% | 490 |
| 900 kcmil | 0.06 | 0.05% | 520 |
| 1000 kcmil | 0.05 | 0.04% | 545 |
How it works
Resistance comes from NEC Chapter 9, Table 8, for stranded conductors at 75 °C. Parallel sets divide the drop by the number of sets. The 2 in the single-phase formula covers the current's path out and back, which is why the length you enter is one way.
What the NEC says about voltage drop
For most circuits, the 3% and 5% figures come from informational notes, such as the one under 210.19(A): a branch circuit sized for no more than 3% drop, and no more than 5% combined across feeder and branch circuit, gives reasonable efficiency. Informational notes are recommendations, not enforceable requirements. Some articles do set hard limits, fire pumps among them, so check the article for the equipment you are wiring.
Limits of this method
Table 8 gives DC resistance. On AC circuits, reactance and skin effect add a little drop that DC resistance does not capture. It is negligible on small conductors and grows on large ones, so for AC feeders of 2/0 and up, treat the result as a slight underestimate or use the effective impedance in Chapter 9, Table 9.
Questions
What is an acceptable voltage drop?
The NEC's informational notes recommend no more than 3% on a branch circuit or feeder and no more than 5% for the two combined. Many designers use 2% for feeders to leave room for the branch circuits.
Is 3% voltage drop a code requirement?
Not for general circuits. The 3% and 5% figures are informational notes, which are advisory. A few articles, such as those for fire pumps and sensitive electronic equipment, set enforceable limits.
How long can a 12 AWG circuit run at 20 amps?
About 45 ft one way on a 120 V circuit before copper 12 AWG reaches 3% drop. A 100 ft run at 20 A drops 7.9 V, or 6.6%, and needs 8 AWG to stay under 3%.
Is the length one way or round trip?
One way. Enter the distance from the panel or source to the load; the formula doubles it for the return path on single-phase and DC circuits.
Why does aluminum need a larger size?
Aluminum has about 61% of copper's conductivity, so for the same drop it needs a larger cross-section, usually two sizes up from copper.
Sources
- NFPA 70, National Electrical Code (NEC). National Fire Protection Association. Free read-only access with a free NFPA account.
Codes are adopted and amended locally. Check the edition in force where you work.
More Electrical calculators
Conduit fill calculator
Fill percentage and the smallest EMT, rigid or PVC conduit for a mix of THHN conductors.
Recessed lighting calculator
How many can lights a room needs, the spacing, where each one goes from the wall, and whether that hits the light level the room wants.
Electrical load calculator
Dwelling service size by the NEC 220.82 optional method, with every demand factor shown.
Wire size & ampacity calculator
Conductor size and breaker from the load, with ambient correction and bundling adjustment applied.
Minimum circuit ampacity calculator
MCA, max breaker and wire size for an AC condenser, heat pump or air handler, from the nameplate amps.
Box fill calculator
Box fill volume by NEC 314.16 for any mix of wires, devices, clamps and grounds, and which boxes are big enough.
Watts to amps calculator
Convert watts to amps for DC, single-phase and three-phase power, with power factor and the breaker it needs.
Amps to watts calculator
Convert amps to watts, kilowatts and VA at any voltage, DC or AC, single- or three-phase.
kVA calculator
kVA to amps, amps to kVA and kW to kVA, single- or three-phase, with the next standard transformer size.
Generator sizing calculator
The generator size a house actually needs, counting one motor start at a time instead of all of them at once.
Breaker size calculator
The breaker a load or motor needs, with the 125% continuous rule, the motor tables and the wire that goes with it.
Electricity cost calculator
What an appliance or a whole list of them costs to run per hour, day, month and year, at your state’s average rate or your own.
EV charging cost calculator
What it costs to charge an electric car at home, at public chargers and at fast chargers, per mile and per month, compared with gas.
Space heater cost calculator
What a space heater costs to run per hour, day, month and winter, and how much electricity it really uses, at your state’s rate.