kVA calculator

Pick what you want to find, then enter what you know. You get the amps, kVA or kW for single- or three-phase power, and the next standard transformer size up.

Single- and three-phasekVA, kW and ampsStandard transformer sizeskVA to amps chart

Inputs

Find
Current
kVA
V
Line to line for three-phase: 208, 240, 480 or 600. Single-phase: 120 or 240.
For kW. 0.8 is the usual rating for generators and mixed loads.

Result

Current
208amps
Next standard three-phase transformer: 75 kVA
kVA
75
kW at PF 0.8
60
Amps at 208 V
208.2
Formula used
I = kVA × 1,000 / (1.732 × V) = 75 × 1,000 / (1.732 × 208) = 208.18 A

Three-phase volts are line to line. Size a real transformer from the load calculation, with room for growth and motor starting.

kVA to amps chart

Full-load amps for standard transformer sizes.

1541.636.11814.4
3083.372.236.128.9
4512510854.143.3
7520818090.272.2
112.5312271135108
150416361180144
225625541271217
300833722361289
5001,3881,203601481
7502,0821,804902722
10002,7762,4061,203962
15004,1643,6081,8041,443
20005,5514,8112,4061,925
25006,9396,0143,0072,406

How it is worked out

Single-phase: kVA = volts x amps / 1,000 amps = kVA x 1,000 / volts Three-phase: kVA = 1.732 x volts x amps / 1,000 amps = kVA x 1,000 / (1.732 x volts) kW = kVA x power factor kVA = kW / power factor

A 75 kVA three-phase transformer at 208 V delivers 75,000 / (1.732 x 208) = 208 A at full load. A 200 A single-phase service at 240 V is 240 x 200 / 1,000 = 48 kVA. A generator rated 80 kW at a power factor of 0.8 is 100 kVA.

kVA or kW?

kW is real power, the part that does work. kVA is apparent power, volts times amps, which is what heats the wires and windings. Transformers, generators and UPS units are rated in kVA because their limit is current, whatever the power factor of the load. For heating and lighting loads kW and kVA are about equal; for motors, kVA is higher.

Standard transformer sizes

Single-phase: 10, 15, 25, 37.5, 50, 75, 100, 167, 250, 333 and 500 kVA. Three-phase: 15, 30, 45, 75, 112.5, 150, 225, 300, 500, 750, 1,000, 1,500, 2,000 and 2,500 kVA. The calculator gives the next size up from your load; the engineer sizes the real transformer from the load calculation, with any growth and motor starting.

For a single circuit in watts, use the watts to amps calculator. For a dwelling service, the electrical load calculator does the NEC 220.82 calculation.

Questions

How do I convert kVA to amps?

Single-phase: kVA x 1,000 / volts. Three-phase: kVA x 1,000 / (1.732 x volts). 75 kVA at 208 V three-phase is 208 A; at 480 V, 90 A.

How many amps is a 45 kVA transformer?

At 208 V three-phase, 125 A; at 480 V, 54 A.

How do I convert kW to kVA?

Divide kW by the power factor. 80 kW at a power factor of 0.8 is 100 kVA.

How many kVA is 100 amps?

24 kVA single-phase at 240 V; 36 kVA three-phase at 208 V and 83 kVA at 480 V.

Is kVA the same as kW?

Only when the power factor is 1. kW = kVA x power factor, so a 100 kVA generator at 0.8 power factor supplies 80 kW.

What size transformer do I need?

Work out the load in kVA and pick the next standard size up: a 60 kVA three-phase load takes a 75 kVA transformer. Leave room for growth and motor starting.

Sources

This calculator uses standard formulas and unit conversions only, all shown on this page. No outside tables or data go into it.

More Electrical calculators

Voltage drop calculator

Drop in volts and percent for copper or aluminum, single-phase, three-phase or DC.

Conduit fill calculator

Fill percentage and the smallest EMT, rigid or PVC conduit for a mix of THHN conductors.

Recessed lighting calculator

How many can lights a room needs, the spacing, where each one goes from the wall, and whether that hits the light level the room wants.

Electrical load calculator

Dwelling service size by the NEC 220.82 optional method, with every demand factor shown.

Wire size & ampacity calculator

Conductor size and breaker from the load, with ambient correction and bundling adjustment applied.

Minimum circuit ampacity calculator

MCA, max breaker and wire size for an AC condenser, heat pump or air handler, from the nameplate amps.

Box fill calculator

Box fill volume by NEC 314.16 for any mix of wires, devices, clamps and grounds, and which boxes are big enough.

Watts to amps calculator

Convert watts to amps for DC, single-phase and three-phase power, with power factor and the breaker it needs.

Amps to watts calculator

Convert amps to watts, kilowatts and VA at any voltage, DC or AC, single- or three-phase.

Generator sizing calculator

The generator size a house actually needs, counting one motor start at a time instead of all of them at once.

Breaker size calculator

The breaker a load or motor needs, with the 125% continuous rule, the motor tables and the wire that goes with it.

Electricity cost calculator

What an appliance or a whole list of them costs to run per hour, day, month and year, at your state’s average rate or your own.

EV charging cost calculator

What it costs to charge an electric car at home, at public chargers and at fast chargers, per mile and per month, compared with gas.

Space heater cost calculator

What a space heater costs to run per hour, day, month and winter, and how much electricity it really uses, at your state’s rate.

Other trades