Recessed lighting calculator
Enter the room and the ceiling. You get the grid, the spacing, where each light goes from the wall, and a check of whether that many lights actually hit the light level the room wants.
Inputs
Estimating assumptions (leave these alone unless you know the fixture)
Result
Light level to aim for, by room
Footcandles are lumens landing on each square foot of the surface you care about. These are the residential levels published by Penn State’s EGEE 102 course, which attributes them to the Illuminating Engineering Society. Ranges are as published: the low end is comfortable ambient light, the high end is task light.
| Room or task | Footcandles | Note |
|---|---|---|
| Living room or bedroom | 10–20 fc | ambient |
| Hallway or entry | 5–20 fc | — |
| Kitchen, general | 30–40 fc | — |
| Kitchen task — stove and sink | 50–100 fc | under-cabinet usually does this |
| Dining room | 30–40 fc | — |
| Bathroom | 20–50 fc | — |
| Home office or reading | 20–50 fc | — |
| Garage, general | 30 fc | — |
| Garage workbench | 100 fc | — |
Spacing and beam spread by ceiling height
Spacing is the ceiling-height-÷-2 rule of thumb. The rest is the diameter of the pool of light each beam angle throws at counter height (2.5 ft above the floor), by trigonometry: 2 × distance × tan(angle ÷ 2). Where the pool is narrower than the spacing, the light scallops instead of reading even.
| Ceiling | Spacing | Pool of light at counter height | |||||
|---|---|---|---|---|---|---|---|
| 15° | 24° | 36° | 40° | 50° | 60° | ||
| 8 ft | 4′ | 1′ 5″ | 2′ 4″ | 3′ 7″ | 4′ | 5′ 2″ | 6′ 4″ |
| 9 ft | 4′ 6″ | 1′ 9″ | 2′ 9″ | 4′ 3″ | 4′ 9″ | 6′ 1″ | 7′ 6″ |
| 10 ft | 5′ | 2′ | 3′ 2″ | 4′ 10″ | 5′ 6″ | 7′ | 8′ 8″ |
| 11 ft | 5′ 6″ | 2′ 3″ | 3′ 7″ | 5′ 6″ | 6′ 2″ | 7′ 11″ | 9′ 10″ |
| 12 ft | 6′ | 2′ 6″ | 4′ | 6′ 2″ | 6′ 11″ | 8′ 10″ | 11′ |
How many lights, by room size
At an 8 ft ceiling on the ÷2 rule, so 4 ft spacing. The grid is fitted to the room, which is why the real spacing differs slightly from 4 ft and why the first light sits half a spacing off the wall.
| Room | Grid | Lights | Actual spacing |
|---|---|---|---|
| 10 × 10 ft | 3 × 3 | 9 | 3′ 4″ × 3′ 4″ |
| 10 × 12 ft | 3 × 3 | 9 | 3′ 4″ × 4′ |
| 12 × 12 ft | 3 × 3 | 9 | 4′ × 4′ |
| 12 × 14 ft | 3 × 4 | 12 | 4′ × 3′ 6″ |
| 12 × 16 ft | 3 × 4 | 12 | 4′ × 4′ |
| 14 × 16 ft | 4 × 4 | 16 | 3′ 6″ × 4′ |
| 14 × 20 ft | 4 × 5 | 20 | 3′ 6″ × 4′ |
| 16 × 20 ft | 4 × 5 | 20 | 4′ × 4′ |
How the layout is worked out
The trade rule is to space the lights at half the ceiling height — 4 ft apart on an 8 ft ceiling, 5 ft on a 10 ft ceiling. It is a rule of thumb, not a code requirement and not a photometric calculation, but it gets the spacing close enough that the room reads evenly lit.
What matters as much is fitting that spacing to the room. Divide the wall by the target spacing and round to a whole number, then use the room divided by that number as the real spacing, and start half a spacing off the wall. A 12 ft wall at 4 ft target gives 3 lights at 4′ with the first 2′ off the wall, so the gap at each end matches the gaps in the middle. Lights pushed hard against the walls wash the walls and leave the middle of the room dim.
The other method, and why it disagrees
Spacing tells you where lights go. It does not tell you whether they are bright enough. For that:
CU is the coefficient of utilization, the share of the lamp’s output that actually lands on the work plane rather than the walls or the inside of the can. LLF is the light loss factor, covering dirt and the lamp dimming with age. A 12 × 14 ft kitchen wants 30 fc. The ÷2 rule puts 12 lights in it, which at 800 lm each works out at about 29 fc — so the lumen method asks for 13. The same room as a living area, wanting 10 fc, is comfortably over with the 12 the rule gives.
That disagreement is the normal case, not a fault. Spacing decides evenness; lumens decide brightness. The calculator shows both and says which one the layout is failing, so you can add a light, buy brighter lamps, or decide the room is a living room and does not need kitchen light.
What this does not do
CU and LLF are estimates here, not lookups. An honest CU comes from the fixture’s own photometric file through the zonal cavity method, and depends on the room’s proportions and how reflective the ceiling, walls and floor are — a dark room can easily sit under 0.4 where a white one is over 0.7. Treat the footcandle figure as a sanity check, not a design. It also assumes one even grid of identical downlights on a flat ceiling, with no daylight, no lamps, no under-cabinet lighting and no wall washing, and takes no account of dimming, glare or colour temperature.
Questions
How far apart should recessed lights be?
The trade rule is half the ceiling height: 4′ apart on an 8 ft ceiling, 4′ 6″ on a 9 ft, 5′ on a 10 ft. Then fit that to the room — divide the wall by the spacing, round to a whole number of lights, and start half a spacing off the wall so the end gaps match the middle ones.
How many recessed lights do I need in a 12x12 room?
9 on an 8 ft ceiling at 4 ft spacing — a 3 × 3 grid. Whether that is bright enough depends on the room: at 800 lm each it is plenty for a living room and short for a kitchen.
How many recessed lights for a 12x14 kitchen?
The spacing rule gives 12 in a 3 × 4 grid. At 800 lm each that is about 29 footcandles, just under the 30 fc a kitchen wants, so the lumen method asks for 13. Add one, or use brighter lamps, or cover the counters with under-cabinet lighting and leave the ceiling at 12.
How far from the wall should the first recessed light be?
Half the spacing. At 4 ft spacing that is 2′ to the centre of the can. The common advice of “2 to 3 ft from the wall” is the same number for an 8 ft ceiling. If the lights are there to wash art or cabinets rather than light the room, move them in to 18–24 in from the wall instead and aim them.
What size recessed lights should I use?
Size is mostly a look: 6 in reads traditional, 4 in and 3 in read modern, 5 in splits the difference. What matters for the layout is the lumens and the beam angle on the box, not the diameter — a 4 in LED can easily out-light an old 6 in can. Buy on lumens and beam angle, choose the diameter on appearance.
What beam angle do I need?
For general ceiling lighting, a flood: 36° to 40°. At counter height from an 8 ft ceiling a 36° beam throws a pool 3′ 7″ across, which nearly meets 4 ft spacing. Narrow beams of 15° to 24° are for highlighting art or a worktop; 50° to 60° wide floods are for low ceilings or when you want to wash a wall.
Can recessed lights touch insulation?
Only if the housing is marked Type IC. NEC 410.116(B) keeps insulation 3 in clear of a luminaire that is not identified for insulation contact, and a non-IC can buried in insulation is a genuine fire risk. In an insulated ceiling buy IC-rated airtight housings; the IECC also wants no more than 2 cfm of air leakage through the fixture.
What is a footcandle?
One lumen landing on one square foot. It is the level of light on the surface, where lumens are the output of the lamp. A kitchen wants 30–40 fc on the counters; a living room is comfortable at 10–20 fc. One footcandle is about 10.76 lux.
Why do two recessed lighting calculators give different answers?
Because they are usually answering different questions. The spacing rule asks where lights go so the room looks even; the lumen method asks how many it takes to hit a light level. They rarely agree, and neither is wrong. This page runs both and tells you which one the layout is failing.
Should recessed lights line up with anything?
Yes, more than most calculators admit. A grid that is mathematically even but lands a light 8 in off a ceiling joist, a duct run or the line of the cabinets will look wrong and may not physically fit. Mark the grid, then check the ceiling framing and the cabinet layout and shift the whole grid a few inches rather than moving one light out of line.
Sources
- IES recommended light levels for homes. Illuminating Engineering Society.
More Electrical calculators
Voltage drop calculator
Drop in volts and percent for copper or aluminum, single-phase, three-phase or DC.
Conduit fill calculator
Fill percentage and the smallest EMT, rigid or PVC conduit for a mix of THHN conductors.
Electrical load calculator
Dwelling service size by the NEC 220.82 optional method, with every demand factor shown.
Wire size & ampacity calculator
Conductor size and breaker from the load, with ambient correction and bundling adjustment applied.
Minimum circuit ampacity calculator
MCA, max breaker and wire size for an AC condenser, heat pump or air handler, from the nameplate amps.
Box fill calculator
Box fill volume by NEC 314.16 for any mix of wires, devices, clamps and grounds, and which boxes are big enough.
Watts to amps calculator
Convert watts to amps for DC, single-phase and three-phase power, with power factor and the breaker it needs.
Amps to watts calculator
Convert amps to watts, kilowatts and VA at any voltage, DC or AC, single- or three-phase.
kVA calculator
kVA to amps, amps to kVA and kW to kVA, single- or three-phase, with the next standard transformer size.
Generator sizing calculator
The generator size a house actually needs, counting one motor start at a time instead of all of them at once.
Breaker size calculator
The breaker a load or motor needs, with the 125% continuous rule, the motor tables and the wire that goes with it.
Electricity cost calculator
What an appliance or a whole list of them costs to run per hour, day, month and year, at your state’s average rate or your own.
EV charging cost calculator
What it costs to charge an electric car at home, at public chargers and at fast chargers, per mile and per month, compared with gas.
Space heater cost calculator
What a space heater costs to run per hour, day, month and winter, and how much electricity it really uses, at your state’s rate.