Amps to watts calculator
Enter the amps and the voltage. You get the watts, kilowatts and VA for DC, single-phase or three-phase power, with the power factor of the load.
Inputs
Result
- Watts
- 1,800
- Kilowatts
- 1.8
- Volts
- 120
- Amps
- 15
- Apparent power
- 1,800 VA
- Horsepower, output equivalent
- 2.41
- Breaker for a continuous load
- 20 A 15 A × 125%
The breaker shown is the smallest standard size (NEC 240.6) for a continuous load at 125%; the wire must be rated for it too.
Amps to watts chart
Watts for common currents, power factor 1.
| Amps | 12 V DC | 120 V | 240 V |
|---|---|---|---|
| 1 A | 12 W | 120 W | 240 W |
| 2 A | 24 W | 240 W | 480 W |
| 2.4 A | 28.8 W | 288 W | 576 W |
| 3 A | 36 W | 360 W | 720 W |
| 5 A | 60 W | 600 W | 1,200 W |
| 7 A | 84 W | 840 W | 1,680 W |
| 10 A | 120 W | 1,200 W | 2,400 W |
| 12 A | 144 W | 1,440 W | 2,880 W |
| 12.5 A | 150 W | 1,500 W | 3,000 W |
| 13 A | 156 W | 1,560 W | 3,120 W |
| 15 A | 180 W | 1,800 W | 3,600 W |
| 16 A | 192 W | 1,920 W | 3,840 W |
| 20 A | 240 W | 2,400 W | 4,800 W |
| 24 A | 288 W | 2,880 W | 5,760 W |
| 25 A | 300 W | 3,000 W | 6,000 W |
| 30 A | 360 W | 3,600 W | 7,200 W |
| 32 A | 384 W | 3,840 W | 7,680 W |
| 40 A | 480 W | 4,800 W | 9,600 W |
| 45 A | 540 W | 5,400 W | 10,800 W |
| 48 A | 576 W | 5,760 W | 11,520 W |
| 50 A | 600 W | 6,000 W | 12,000 W |
| 60 A | 720 W | 7,200 W | 14,400 W |
| 70 A | 840 W | 8,400 W | 16,800 W |
| 80 A | 960 W | 9,600 W | 19,200 W |
| 100 A | 1,200 W | 12,000 W | 24,000 W |
| 125 A | 1,500 W | 15,000 W | 30,000 W |
| 150 A | 1,800 W | 18,000 W | 36,000 W |
| 200 A | 2,400 W | 24,000 W | 48,000 W |
How to convert amps to watts
A 15 A circuit at 120 V carries up to 15 x 120 = 1,800 W. A 30 A dryer circuit at 240 V carries 7,200 W. A 20 A three-phase load at 208 V with a power factor of 0.9 is 1.732 x 20 x 208 x 0.9 = 6,485 W.
Watts and VA
Volts times amps gives volt-amperes (VA), the apparent power. For heaters and lights they are the same as watts. For motors and electronics the watts are lower, by the power factor. Generators, UPS units and transformers are rated in VA or kVA because the current, not just the real power, is what heats their windings.
Going the other way? Use the watts to amps calculator. For a generator, the generator sizing calculator adds up running and starting watts.
Questions
How many watts is 1 amp?
120 watts at 120 V, 240 watts at 240 V and 12 watts at 12 V. Watts = amps x volts.
How many watts is 30 amps?
3,600 W at 120 V and 7,200 W at 240 V. For a continuous load, 80% of that: 5,760 W at 240 V.
How many watts is 13 amps?
1,560 W at 120 V, 3,120 W at 240 V, and 2,990 W at the 230 V used in the UK, where 13 A is the plug fuse rating.
How many watts is 20 amps?
2,400 W at 120 V and 4,800 W at 240 V; 1,920 W and 3,840 W for a continuous load.
How do I convert amps to kilowatts?
Multiply amps by volts and divide by 1,000. For three-phase, multiply by 1.732 as well, and for AC by the power factor. 50 A at 240 V is 12 kW.
How many watts is 50 amps?
6,000 W at 120 V and 12,000 W, or 12 kW, at 240 V. A 50 A circuit for a continuous load, such as an EV charger, is limited to 80%: 40 A, or 9,600 W at 240 V.
How many watts is 5 amps?
600 W at 120 V, 1,200 W at 240 V and 60 W at 12 V DC.
How many watts is 12.5 amps?
1,500 W at 120 V, which is why a 1,500 W space heater draws 12.5 A, and 3,000 W at 240 V.
How many watts is 100 amps?
24,000 W, or 24 kW, at 240 V single-phase. A 100 A service can't run that continuously; the NEC load calculation decides what it can carry.
Sources
This calculator uses standard formulas and unit conversions only, all shown on this page. No outside tables or data go into it.
More Electrical calculators
Voltage drop calculator
Drop in volts and percent for copper or aluminum, single-phase, three-phase or DC.
Conduit fill calculator
Fill percentage and the smallest EMT, rigid or PVC conduit for a mix of THHN conductors.
Recessed lighting calculator
How many can lights a room needs, the spacing, where each one goes from the wall, and whether that hits the light level the room wants.
Electrical load calculator
Dwelling service size by the NEC 220.82 optional method, with every demand factor shown.
Wire size & ampacity calculator
Conductor size and breaker from the load, with ambient correction and bundling adjustment applied.
Minimum circuit ampacity calculator
MCA, max breaker and wire size for an AC condenser, heat pump or air handler, from the nameplate amps.
Box fill calculator
Box fill volume by NEC 314.16 for any mix of wires, devices, clamps and grounds, and which boxes are big enough.
Watts to amps calculator
Convert watts to amps for DC, single-phase and three-phase power, with power factor and the breaker it needs.
kVA calculator
kVA to amps, amps to kVA and kW to kVA, single- or three-phase, with the next standard transformer size.
Generator sizing calculator
The generator size a house actually needs, counting one motor start at a time instead of all of them at once.
Breaker size calculator
The breaker a load or motor needs, with the 125% continuous rule, the motor tables and the wire that goes with it.
Electricity cost calculator
What an appliance or a whole list of them costs to run per hour, day, month and year, at your state’s average rate or your own.
EV charging cost calculator
What it costs to charge an electric car at home, at public chargers and at fast chargers, per mile and per month, compared with gas.
Space heater cost calculator
What a space heater costs to run per hour, day, month and winter, and how much electricity it really uses, at your state’s rate.